dc.description.abstractThe discussion on fire safety is necessary in Brazilian buildings. Current legislation requires construction with compartmentalized areas separated by walls with structural ceramic blocks capable of resisting fire for an amount of time pre-determined in norm NBR 14432 (ABNT, 2001). However, a lack of building standards requires experimental tests according to NBR 5628 (ABNT, 2001) to determine the necessary configuration to achieve fire resistance. For this purpose, this study analyzed the effect of fire on structural walls covered with a mortar coating. Experiments were conducted in real scale in a standardized vertical oven and the fire growth curve of ISO 834 (ISO, 1999). Three types of walls were tested, each with a different mortar coating: (a) lime; (b) 0.6 kg/m3 polypropylene fiber and 1.2 kg/m3 polypropylene fiber. The mortar coatings were 1.5 cm thick on the side facing the fire and 2.5 cm thick in the outside. The wall was composed of structural blocks measuring 14 cm x 19 cm x 29 cm. Fire experiments evaluated the structure stability, impermeability to hot gases and smoke and thermal insulation of each sample. Results showed that the structural system with 1.2 kg/m3 polypropylene fiber mortar coating obtained the best thermal insulation effect with the longest fire resistance time of 176 min.spa
dc.description.abstractLa discusión sobre seguridad contra incendios es necesaria en los edificios brasileños. La legislación actual exige la construcción con áreas compartimentadas separadas por muros con bloques cerámicos estructurales capaces de resistir el fuego por un tiempo predeterminado en la norma NBR 14432 (ABNT, 2001). Sin embargo, la falta de estándares de construcción requiere pruebas experimentales según NBR 5628 (ABNT, 2001) para determinar la configuración necesaria para lograr la resistencia al fuego. Para ello, este estudio analizó el efecto del fuego en los muros estructurales revestidos con un revestimiento de mortero. Los experimentos se realizaron a escala real en un horno vertical estandarizado y la curva de crecimiento del fuego de ISO 834 (ISO, 1999). Se ensayaron tres tipos de muros, cada uno con un revestimiento de mortero diferente: (a) cal; b) 0,6 kg / m3 de fibra de polipropileno y 1,2 kg / m3 de fibra de polipropileno. Los revestimientos de mortero tenían 1,5 cm de espesor en el lado de cara al fuego y 2,5 cm de espesor en el exterior. El muro estaba compuesto por bloques estructurales de 14 cm x 19 cm x 29 cm. Los experimentos de fuego evaluaron la estabilidad de la estructura, la impermeabilidad a los gases calientes y el humo y el aislamiento térmico de cada muestra. Los resultados mostraron que el sistema estructural con revestimiento de mortero de fibra de polipropileno de 1,2 kg / m3 obtuvo el mejor efecto de aislamiento térmico con el tiempo de resistencia al fuego más largo de 176 min.spa
dc.format.mimetypeapplication/pdfspa
dc.language.isoengspa
dc.publisherCorporación Universidad de la Costaspa
dc.rightsCC0 1.0 Universal*
dc.rights.urihttp://creativecommons.org/publicdomain/zero/1.0/*
dc.sourceRevista de la Construccionspa
dc.subjectFire resistancespa
dc.subjectFire safetyspa
dc.subjectLimespa
dc.subjectPolypropylene fiberspa
dc.subjectResistente al fuegospa
dc.subjectSeguridad contra incendiosspa
dc.subjectLimaspa
dc.subjectFibra de polipropilenospa
dc.titleExperimental analysis of fire resistance of mortar coatings on structural masonry wallsspa
dc.title.alternativeAnálisis experimental de resistencia al fuego de revestimientos de mortero en muros de mampostería estructuralspa
dc.typearticlespa
dcterms.referencesAndrade, J.&Tutikian, B. (2011). Resistência mecânica do concreto. In: ISAIA, GeraldoCechella. Concreto: Ciência e Tecnologia. São Paulo: IBRACON, Brazil. Ch. 17. p. 615-651.spa
dcterms.referencesAssociação Nacional Da Indústria Cerâmica. (2015).ANICER. Retrieved from: <http://www.anicer.com.br>. Date viewed: 24 nov. 2015.spa
dcterms.referencesAssociação Brasileiras De Normas Técnicas.(2001).NBR 5628: Componentes construtivos estruturais -Determinação da resistência ao fogo. Rio de Janeiro.spa
dcterms.referencesAssociação Brasileiras De Normas Técnicas.(2013). NBR 15575: Edificações habitacionais –Desempenho. Parte 4: Requisitos para os sistemas de vedações verticais internas e externas -SVVIE. Rio de Janeiro.spa
dcterms.referencesAssociação Brasileiras De Normas Técnicas.(2005). NBR 15259: Argamassa para assentamento e revestimento de paredes e tetos –Determinação da absorção de água por capilaridade e do coeficiente de capilaridade. Rio de Janeiro.spa
dcterms.referencesAssociação Brasileiras De Normas Técnicas.(2002). NBR NM 47: Concreto -determinação do teor de ar em concretos frescos –Método pressométrico. Rio de Janeirospa
dcterms.referencesAssociação Brasileiras De Normas Técnicas.(2016). NBR 13276: Argamassa para assentamento e revestimento de paredes e tetos –Determinação do índice de consistência. Rio de Janeirospa
dcterms.referencesAssociação Brasileiras De Normas Técnicas. (2005). NBR 13278: Argamassa para assentamento de paredes e revestimento de paredes e tetos –Determinação da densidade de massa e do teor de ar incorporado. Rio de Janeiro.spa
dcterms.referencesAssociação Brasileiras De Normas Técnicas.(2005). NBR 13279: Argamassa para assentamento de paredes e revestimento de paredes e tetos –Determinação da resistência à tração na flexão e à compressão. Rio de Janeirospa
dcterms.referencesAssociação Brasileiras De Normas Técnicas.(2005). NBR 13280: Argamassapara assentamento e revestimento de paredes e tetos –Determinação da densidade de massa aparente no estado endurecido. Rio de Janeirospa
dcterms.referencesAssociação Brasileiras De Normas Técnicas.(2005).NBR 13281: Argamassa para assentamento de paredes e revestimento de paredes e tetos –Requisitos. Rio de Janeiro.spa
dcterms.referencesAssociação Brasileiras De Normas Técnicas. (2005). NBR 9778: Argamassa e concreto endurecidos –Determinação da absorção de água, índices de vazios e massa específica. Rio de Janeirospa
dcterms.referencesAgopyan, V.,Souza, U. E. L.,Paliari, J. C.,&Andrade, A. C. (2009). Alternativas para redução do desperdício de materiais nos canteiros de obraspa
dcterms.referencesAl-Hadhrami, L. M. &Ahmad, A. (2009). Assessment of thermal performance of different types of masonry bricks used in Saudi Arabia. Applied Thermal Engineering, 29.spa
dcterms.referencesAmaral, E. C.,Botelho, R. A.,Lameiras, F. S.,Reis, S. C.&Tolentino, E. (2012).O efeito do tratamento térmico a 300 °C na conectividade da estrutura de poros de argamassas de cimento Portland reforçadas por fibras de polipropileno. Órgão oficial da associação brasileira de cerâmica -ano lviii -v. 58, 346 -abr/mai/jun 2012.spa
dcterms.referencesArandigoyen, M.&Alvarez, J. I. (2007). Pore structure and mechanical properties of cement–lime mortars. Cement and Concrete Research, 37(5), 767-775.spa
dcterms.referencesAyala, F. R. R. (2010). Mechanical properties and structural behaviour of masonry at elevated temperatures, Ph.D. Thesis, University of Manchester.spa
dcterms.referencesBendjillali, K,; Goual, M. S.,Chemrouk, M.&Damene, Z. (2011). Study of the reinforcement of limestone mortars by polypropylene fibers waste. Physics Procedia 21, 42-46.spa
dcterms.referencesCamacho, J. S. (2006). Projeto de edifícios de alvenaria estrutural. Núcleo de Ensino e Pesquisa da Alvenaria Estrutural -NEPAE, Ilha Solteira, São Paulo.spa
dcterms.referencesCentofante, G.&Dagostini, C. M. (2014). Análise das propriedades de argamassa de revestimento com adição de fibras de polipropileno. Joaçaba: Unoesc & Ciência -Acetspa
dcterms.referencesComité Européen de Normalisation (Cen). (2005).EN 1996-1-1: Eurocode 6 -Design of masonry structures -Part 1-2: General rules -Structural fire design. Brusselsspa
dcterms.referencesCosta, C. N.&Silva, V. P. (2006). Revisão histórica das curvas padronizadas de incêndio. In: Seminário Internacional NUTAU: Tecnologia de Durabilidade, 2006, São Paulo. Resumos. São Paulo: NUTAU-USPspa
dcterms.referencesDawood, E. T.&Ramli, M. (2011). Contribution of hybrid fibers on the properties of high strength concrete having high workability. ProcediaEngineering, 14, 814-820.spa
dcterms.referencesEzziane, M.,Kadri, T.,Molez, L.,Jauberthie, R.&Belhacen, A. (2015). High temperature behaviour of polypropylene fibres reinforced mortars. Fire Safety Journal71,324-331.spa
dcterms.referencesGil, A., Pacheco, F., Christ, R., Bolina, F., Khayat, K. H., & Tutikian, B. (2017). Comparative study of concrete panels’ fire resistance. ACI Materials Journal, 114(5), doi:https://doi.org/10.14359/51689715spa
dcterms.referencesIngham, J. (2009). Forensic Engineering of Fire-Damaged Structures. ICE, 162, 12-17spa
dcterms.referencesInternational Organization For Standardization (ISO). (1999). ISO 834: fire resistance tests –Elements of building construction. Genevaspa
dcterms.referencesKarahan, O. (2011). Residual compressive strength of fire-damaged mortar after post-fire-air-curing. Fire and Material, 35(8), 561-567spa
dcterms.referencesMetha, P. K.&Monteiro, P. J. M. (2014).Concreto: microestrutura, propriedades e materiais. 3. ed. São Paulo: IBRACON.spa
dcterms.referencesMonte, R.,Barros, M.&Figueiredo, A. (2012). Avaliação da influência de fibras de polipropileno na resistência de aderência de revestimentos de argamassa. São Paulo,Brazil.12 pspa
dcterms.referencesMorsy, M. S.,Al-Salloum, Y.A.,Abbas, H.&Alsayed, S. H. (2012). Behavior of blended cement mortars containing nano-metakaolin at elevated temperatures. Construction and Building Materials.35, 900–905.spa
dcterms.referencesNguyen, T. D.&Meftah, F.(2012). Behavior of clay hollow-brick masonry walls during fire. Part1: experimental analysis.Fire Safety Journal, 52,55-64.spa
dcterms.referencesOliveira, M. L. L. (2001). Influência da adição de fibras de polipropileno em argamassas. 2001. Master’s Thesis. Pós-Graduação em Engenharia Civil. Universidade Federal de Santa Catarina, Florianópolis.Brazilspa
dcterms.referencesPacheco, F., Christ, R., Quinino, U., & Tutikian, B. F. (2018). Effects of fiber hybridization in advanced cementitious composites durability in humid and aggressive environments. Revista Materia,23.doi: https://doi.org/10.1590/s1517-707620180003.0505.spa
dcterms.referencesPacheco, F.Christ, R.Gil, A.M. &Tutikian, B.F (2016).SEM and 3D microtomography application to investigate the distribution of fibers in advanced cimenticious composites. Revista Ibracon de Estruturas e Materiais,9,824-832, doi:10.1590/s1983-41952016000600002spa
dcterms.referencesPachta, V.,Triantafyllaki, S.&Stefanidou, M. (2018). Performance of lime-based mortars at elevated temperatures. Construction and Building Materials,189, 576-584.spa
dcterms.referencesPinheiro, B. C. A.&Holanda, J. N. F. (2010). Efeito da temperatura de queima em algumas propriedades mecânicas de cerâmica vermelha. Universidade Estadual do Norte Fluminense, CCT-LAMAV, Grupo de Materiais Cerâmicos.Brazil.spa
dcterms.referencesRigão, A. O. (2012). Comportamento de pequenas paredes de alvenaria estrutural frente a altas temperaturas. Master’s Thesis in Civil Engineering. Universidade Federal de Santa Maria, Santa Maria, RS.Brazil.spa
dcterms.referencesRusso, S.&Sciarretta, F. (2012). Experimental and theoretical investigation on masonry after high temperature exposure.Experimental Mechanics, 52(4), 341-359.spa
dcterms.referencesSilva, R. P.&Barros, M. M. S. B. (2007). Revestimentos de argamassa com fibras de polipropileno. Revista Téchne. São Paulo, n. 127. Retrieved from: <http://techne.pini.com.br/engenharia-civil/127/artigo287483-1.aspx>. Date viewed: 14 may 2017spa
dcterms.referencesSouza, R. P. (2017). Avaliação da influência da espessura do revestimento argamassado e do carregamento no comportamento de alvenaria frente a altas temperaturas. São Leopoldo, 2017. 133p. Dissertação (Mestrado em Engenharia Civil) –Programa de Pós-Graduação em Engenharia Civil, Unisinos, São Leopoldo.spa
dcterms.referencesTiscoski, B. L.,&Antunes, E. G. P. (2007).Análise do efeito da adição de fibras de polipropileno da resistência de aderência à tração em argamassa de revestimento. Undergraduate Thesis in Civil Engineering, UNESC –Universidade do Extremo SulCatarinensespa
dcterms.referencesYazici, S., Sezer, G. I., &Sengul, H. (2012). The effect of high temperature on the compressive strength of mortars. Construction and Building Materials. 35, 97–100.spa
dcterms.referencesZhang, H.,Liu, Y.,Sun, H.&Shoufeng, W. (2016). Transient dynamic behavior of polypropylene fiber reinforced mortar under compressive impact loading.Construction and Building Materials,111, 30-42.spa
dc.source.urlhttps://www.scopus.com/record/display.uri?eid=2-s2.0-85100138568&doi=10.7764%2fRDLC.19.3.311&origin=inward&txGid=3c23848123d420801907609acd5ae05bspa
dc.rights.accessrightsinfo:eu-repo/semantics/openAccessspa
dc.identifier.doi10.7764/RDLC.19.3.311
dc.type.hasversioninfo:eu-repo/semantics/publishedVersionspa


Files in this item

Thumbnail
Thumbnail

This item appears in the following Collection(s)

Show simple item record

CC0 1.0 Universal
Except where otherwise noted, this item's license is described as CC0 1.0 Universal